M12700-1 v5
Table 140. Event list
Function Value
Buffer capacity Maximum number of events in the list 5000
Resolution 1 ms
Accuracy Depending on time synchronizing
M13765-1 v6
Table 141. Indications
Function Value
Buffer capacity Maximum number of indications
presented for single disturbance
352
Maximum number of recorded
disturbances
200
M12702-1 v5
Table 142. Event recorder
Function Value
Buffer capacity Maximum number of events in
disturbance report
150
Maximum number of disturbance
reports
200
Resolution 1 ms
Accuracy Depending on time synchronizing
M13747-1 v6
Table 143. Trip value recorder
Function Value
Buffer capacity
Maximum number of analog inputs 30
Maximum number of disturbance
reports
200
M12384-1 v8
Table 144. Disturbance recorder
Function Value
Buffer capacity Maximum number of analog inputs 40
Maximum number of binary inputs 352
Maximum number of disturbance reports 200
Maximum total recording time (3.4 s recording time and maximum
number of channels, typical value)
340 seconds (100 recordings) at 50 Hz
280 seconds (80 recordings) at 60 Hz
Generator protection REG670
1MRK 502 074-BEN M
Version 2.2
116 Hitachi Power Grids
© Copyright 2017 Hitachi Power Grids. All rights reserved