Injection equipment
GUID-87197CB5-8590-4872-A5B6-8C6D2A815C9E v4
Table 32. Electromagnetic compatibility tests
Test Type test values Reference standards
1 MHz burst disturbance 2.5 kV IEC 60255-26
100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEC 60255-26
IEC 61000-4-2, Class IV
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEEE/ANSI C37.90.3
Fast transient disturbance test 4 kV IEC 60255-26, Zone A
Surge immunity test 1-2 kV, and 2-4 kV, 1.2/50 µs
High energy
IEC 60255-26, Zone A
Power frequency immunity test 150-300 V, 50 Hz IEC 60255-26, Zone A
Power frequency magnetic field test 1000 A/m, 3 s
100 A/m, cont.
IEC 61000-4-8
Radiated electromagnetic field disturbance test 20 V/m, 80-1000 MHz
1.4-2.7 GHz
IEC 60255-26
Radiated electromagnetic field disturbance test 20 V/m, 80-1000 MHz IEEE/ANSI C37.90.2
Conducted electromagnetic field disturbance test 10 V, 0.15-80 MHz IEC 60255-26
Voltage dips and short interruptions Dips:
40% /200 ms
70% /500 ms
Interruptions:
0-50 ms: No restart
0… ∞ s: Correct behaviour
at power down
IEC 60255-26
Radiated emission 30-1000 MHz IEC 60255-26
Conducted emission 0.15-30 MHz IEC 60255-26
Table 33. Insulation tests, REX060, REX062 and REG670
Test
Type test values Reference standard
Dielectric test 2.0 kV AC, 1 min IEC 60255-27
Impulse voltage test 5.0 kV, 1.2/50 µs, 0.5 J IEC 60255-27
Insulation resistance >100 MΩ at 500V DC IEC 60255-27
Generator protection REG670
1MRK 502 074-BEN M
Hitachi Power Grids 67
© Copyright 2017 Hitachi Power Grids. All rights reserved