14 SOI/266-XC Rev. I | 2600T Series Pressure transmitters
5 Applications
5.3 Liquid level measurements on closed tanks and
non condensable fluids (dry leg)
Mount the transmitter at the same height or below the lowest
level to be measured.
Connect the + (H) side of the transmitter to the bottom of the
tank.
Connect the - (L) side of the transmitter to the upper part of the
tank, above the maximum level of the tank.
Figure 10: Level measurement on closed tank with dry leg
5.4 Liquid level measurement with open tanks
Mount the transmitter at the same height or below the lowest
level to be measured.
Connect the + (H) side of the transmitter to the bottom of the
tank.
Vent the “–” (L) side of the transmitter to the atmosphere (in this
case a gauge pressure is shown; the (L) side is already vented to
the atmosphere).
Figure 11: Level measurement on open tank with P style transmitter
5.5 Pressure or absolute pressure measurement of a
condensable vapor in a pipe
Place the tap at the side of the line.
Mount the transmitter below the tap.
Connect the + (H) side of the transmitter to the pipe.
Fill the vertical section of the connecting line to the tap with a
compatible liquid through the dedicated filling tee.
Figure 12: Pressure measurement with DP and P style transmitters