3.16.3 QTY_GOOSE_COMM function block
3.16.3.1 Function block
GUID-0FDC082E-C9A8-4B02-9878-6C49E44B7C0E V1 EN
Figure 56: Function block
3.16.3.2 Functionality
The QTY_GOOSE_COMM function block evaluates the peer device communication
status from the quality bits of the input signal and passes it as a Boolean signal to the
application.
The IN input can be connected to any GOOSE application logic output signal, for
example, GOOSERCV_BIN.
The OUT output indicates the communication status of the GOOSE function block. When
the output is in the true (1) state, the GOOSE communication is active. The value false (0)
indicates communication timeout.
3.16.3.3 Signals
Table 81: QTY_GOOSE_COMM Input signals
Name
Type Default Description
IN Any 0 Input signal
Table 82: QTY_GOOSE_COMM Output signals
Name
Type Description
COMMVALID BOOLEAN Output signal
1MAC059074-MB A Section 3
Basic functions
615 series ANSI 143
Technical Manual