ABB 615 Series - Three-Phase Voltage-Dependent Overcurrent Protection 51 V; Function Block; Functionality; Identification

ABB 615 Series
1196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 258: 67/51P Technical revision history
Technical revision Change
B Added a new input NON_DIR
C Step value changed from 0.05 to 0.01 for the
Time
multiplier
setting.
D Monitored data VMEM_USED indicating voltage
memory use.
E Internal improvement.
4.1.3 Three-phase voltage-dependent overcurrent protection 51V
4.1.3.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase voltage-dependent
overcurrent protection
PHPVOC 3I(U)> 51V
4.1.3.2 Function block
TRIP
PICKUPI_B
51V
I_C
V_BC
V_AB
V_CA
I_A
BLOCK
ENA_MULT
ENA_U_MULT
GUID-6290E1B0-0380-40DD-A5AF-60D789C30DF2 V1 EN
Figure 126: Function block
4.1.3.3 Functionality
The three-phase voltage-dependent overcurrent protection function 51V is used for
single-phase, two-phase or three-phase voltage-dependent time overcurrent protection of
generators against overcurrent and short circuit conditions.
The function picks up when the input phase current exceeds a limit which is dynamically
calculated based on the measured terminal voltages. The operating characteristics can be
selected to be either inverse definite minimum time IDMT or definite time DT.
Section 4 1MAC059074-MB A
Protection functions
258 615 series ANSI
Technical Manual