Figure 147: The influence of Weighting factor p at prior load 1xFLC, timeconstant =
640 s, and Overload factor = 1.05
Setting the overload factor
The value of Overload factor defines the highest permissible continuous load. The
recommended value is 1.05.
1MAC059074-MB A Section 4
Protection functions
615 series ANSI 309
Technical Manual