Vector group matching and elimination of the zero-sequence component
The vector group of the power transformer is numerically matched on the high voltage and
low voltage sides by means of the Winding 1 type, Winding 2 type and Clock number
settings. Thus no interposing CTs are needed if there is only a power transformer inside
the protected zone. The matching is based on phase shifting and a numerical delta
connection in the protection relay. If the neutral of a star-connected power transformer is
grounded, any ground fault in the network is perceived by the protection relay as a
differential current. The elimination of the zero-sequence component can be selected for
that winding by setting the Zro A elimination parameter.
Table 432: 87T settings corresponding to the power transformer vector groups and zero-sequence
elimination
Vector group of the
transformer
Winding 1 type Winding 2 type Clock number Zro A Elimination
Yy0 Y y Clk Num 0 Not needed
YNy0 YN y Clk Num 0 HV side
YNyn0 YN yn Clk Num 0 HV & LV side
Yyn0 Y yn Clk Num 0 LV side
Yy2 Y y Clk Num 2 Not needed
YNy2 YN y Clk Num 2 Not needed
YNyn2 YN yn Clk Num 2 Not needed
Yyn2 Y yn Clk Num 2 Not needed
Yy4 Y y Clk Num 4 Not needed
YNy4 YN y Clk Num 4 Not needed
YNyn4 YN yn Clk Num 4 Not needed
Yyn4 Y yn Clk Num 4 Not needed
Yy6 Y y Clk Num 6 Not needed
YNy6 YN y Clk Num 6 HV side
YNyn6 YN yn Clk Num 6 HV & LV side
Yyn6 Y yn Clk Num 6 LV side
Yy8 Y y Clk Num 8 Not needed
YNy8 YN y Clk Num 8 Not needed
YNyn8 YN yn Clk Num 8 Not needed
Yyn8 Y yn Clk Num 8 Not needed
Yy10 Y y Clk Num 10 Not needed
YNy10 YN y Clk Num 10 Not needed
YNyn10 YN yn Clk Num 10 Not needed
Yyn10 Y yn Clk Num 10 Not needed
Yd1 Y d Clk Num 1 Not needed
Table continues on next page
Section 4 1MAC059074-MB A
Protection functions
520 615 series ANSI
Technical Manual