Table 540: 47 Output signals
Name Type Description
TRIP BOOLEAN Trip
PICKUP BOOLEAN Pickup
4.5.4.7 Settings
Table 541: 47 Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Pickup value 0.010...1.000 xUn 0.001 0.030 Pickup value
Trip delay time 40...120000 ms 1 40 Trip delay time
Table 542: 47 Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Table 543: 47 Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
4.5.4.8 Monitored data
Table 544: 47 Monitored data
Name
Type Values (Range) Unit Description
PICKUP_DUR FLOAT32 0.00...100.00 % Ratio of pickup time / trip time
47 Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
1MAC059074-MB A Section 4
Protection functions
615 series ANSI 635