EasyManua.ls Logo

ABB 615 Series - Settings

ABB 615 Series
1196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.5.8.7 Settings
Table 574: 78V Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Pickup value 2.0...30.0 deg 0.1 6.0 Pickup value for vector shift
Table 575: 78V Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Over Volt Blk value 0.40...1.50 xUn 0.01 1.20 Voltage above which function will be internally
blocked
Under Volt Blk value 0.15...1.00 xUn 0.01 0.80 Voltage below which function will be internally
blocked
Table 576: 78V Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Table 577: 78V Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Phase supervision 7=Ph A + B + C
8=Pos sequence
8=Pos sequence Monitored voltage phase
1MAC059074-MB A Section 4
Protection functions
615 series ANSI 671
Technical Manual

Table of Contents

Other manuals for ABB 615 Series

Related product manuals