Table 729: SOTF Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
SOTF reset time 0...60000 ms 1 1000 SOTF detection period after initialization
Table 730: SOTF Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
5.8.8 Monitored data
Table 731: SOTF Monitored data
Name Type Values (Range) Unit Description
SOTF Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
5.8.9 Technical data
Table 732: SOTF Technical data
Characteristic
Value
Trip time accuracy ±1.0% of the set value or ±20 ms
Section 5 1MAC059074-MB A
Protection related functions
834 615 series ANSI
Technical Manual