Parameter Values (Range) Unit Step Default Description
Pressure alarm time 0...60000 ms 1 10 Time delay for gas pressure alarm in ms
Pres lockout time 0...60000 ms 10 10 Time delay for gas pressure lockout in ms
Ini inactive days 0...9999 1 0 Initial value of the inactive days counter
Inactive Alm hours 0...23 h 1 0 Alarm time of the inactive days counter in hours
7.1.8 Monitored data
Table 787: 52CM Monitored data
Name Type Values (Range) Unit Description
T_TRV_OP FLOAT32 0...60000 ms Travel time of the CB during
opening operation
T_TRV_CL FLOAT32 0...60000 ms Travel time of the CB during
closing operation
T_SPR_CHR FLOAT32 0.00...99.99 s The charging time of the CB
spring
NO_OPR INT32 0...99999 Number of CB operation cycle
INA_DAYS INT32 0...9999 The number of days CB has
been inactive
CB_LIFE_A INT32 -99999...99999 CB Remaining life phase A
CB_LIFE_B INT32 -99999...99999 CB Remaining life phase B
CB_LIFE_C INT32 -99999...99999 CB Remaining life phase C
IPOW_A FLOAT32 0.000...30000.00
0
Accumulated currents power
(Iyt), phase A
IPOW_B FLOAT32 0.000...30000.00
0
Accumulated currents power
(Iyt), phase B
IPOW_C FLOAT32 0.000...30000.00
0
Accumulated currents power
(Iyt), phase C
52CM Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
1MAC059074-MB A Section 7
Condition monitoring functions
615 series ANSI 895
Technical Manual