EasyManua.ls Logo

ABB 650 series - Page 90

ABB 650 series
130 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Creating a complete HMI display page
Procedure:
1. Make a sketch how to present the single line diagram.
2. Place the apparatus, transformer and other symbols that are needed for the single
line diagram into the raster boxes.
3. Add connection points where needed.
4. Link the apparatus symbols with line elements.
5. Adjust the text symbols while writing to north, east, south or west. Use the object
property window to do it.
6. Place measurements when needed.
7. Edit the name, unit and number of decimals of the measurements.
8. Select each object that has a dynamic link and do the link to the corresponding
process object, see Figure 57.
9. Check to select the correct function block. Function blocks of the same type can
have different instance numbers.
10. Validate that all links are done.
11. Save the complete picture.
12. Repeat the steps for all pages when more than one is needed.
13. Write the display configuration to IED from the GDE tool.
IEC09000666-1-en.vsd
IEC09000666 V1 EN
Figure 57: GDE: Establish a dynamic object link
Linking process objects
To describe a process object within an IED it needs to be established in the application
configuration, configured when given with its parameters by PST and linked to be
displayed in the HMI.
Three tools are involved for the described steps:
Section 6 1MRK 511 284-UEN A
Local HMI engineering
84 650 series
Engineering manual

Table of Contents