ACT to program the application function block for apparatus and/or
measurements.
PST to adapt the settings and/or configuration parameter of the application
function block.
GDE to establish the link for updating the selected data attribute in the HMI of the
application function block.
The following application function blocks are used to deliver the needed information:
Switch controller (of type CSWI) for an apparatus.
All configured function blocks with measurements (of type MMXU) for the
measurements.
VSGGIO for one bit indications for the dynamic text symbols.
SLGGGIO for 32 bit indications for the dynamic text symbols.
Procedure
1. Right-click the apparatus symbol and select Select Input Signal. A list of
engineered switch control application function blocks opens, see Figure 58.
2. Select the switch control application function block that corresponds to the
selected apparatus.
3. Right-click the measurement symbol and select Select Input Signal. A list of the
engineered measurement application function blocks opens.
4. Select the measurement application function block that corresponds to the
selected symbol.
1MRK 511 284-UEN A Section 6
Local HMI engineering
650 series 85
Engineering manual