EasyManua.ls Logo

ABB 650 series - Setting Guidelines; Comparator for Integer Inputs - INTCOMP; Identification; Application

ABB 650 series
320 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Settable time limits for warning and alarm are provided. The time limit for
overflow indication is fixed to 999999.9 seconds.
9.12.3 Setting guidelines
GUID-2911D624-87D5-4427-BB2F-E0D1072394FA v3
The settings tAlarm and tWarning are user settable limits defined in seconds. The
achievable resolution of the settings depends on the level of the values defined.
A resolution of 10 ms can be achieved when the settings are defined within the
range
1.00 second ≤ tAlarm99 999.99 seconds
1.00 second ≤ tWarning99 999.99 seconds.
If the values are above this range, the resolution becomes lower due to the 32 bit
float representation
99 999.99 seconds < tAlarm999 999.0 seconds
99 999.99 seconds < tWarning999 999.0 seconds
Note that tAlarm and tWarning are independent settings, that is,
there is no check if tAlarm > tWarning.
The limit for the overflow supervision is fixed at 999999.9 seconds.
9.13 Comparator for integer inputs - INTCOMP
9.13.1 Identification
GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Comparison of integer values INTCOMP Int<=>
9.13.2 Application
GUID-4C6D730D-BB1C-45F1-A719-1267234BF1B9 v1
The function gives the possibility to monitor the level of integer values in the
system relative to each other or to a fixed value. It is a basic arithmetic function
that can be used for monitoring, supervision, interlocking and other logics.
1MRK 511 423-UEN A Section 9
Logic
Bay control REC650 2.2 IEC 189
Application manual

Table of Contents

Other manuals for ABB 650 series

Related product manuals