Appendix F Password Update Procedure Password Update Procedure on the Data Collector:
2PAA107563-600 B 175
c. After successful removal, run the following command to install services.
"%app_root%\config\application\APP_Install_Services" /install all
d. In Windows Services configuration, set the startup type of the RTDB main
service RTDB <RTDBDatabaseDrive>:\RTDBData to Automatic.
6. Login to History Server and open Credential Manager by navigating to
Control Panel > User Accounts.
7. Select the Generic Credential corresponding to the Data Collector updated with
password (for example, CPIMS_DC/<DCNName>_DBADMIN).
8. Use the Edit option and update the password. Save and close Credential
Manager.
9. Start the RTDB services from the Data Collector.
10. Open Plant Explorer. Navigate to Service Structure and update the new
password in Special Configuration tabs of 800xA History SyncService, 800xA
History Event Collector and 800xA History EventServer Services and restart
the services.