LED State Color LED = OFF LED = ON
Outputs O0...O3 Digital output Yellow Output is OFF Output is ON
(The output
voltage (normally
24 V DC) is
only displayed if
UP/ZP and L+/M
(supply voltages
for the module) are
switched ON)
The system data of AC500-eCo V3 apply
Ä
Chapter 2.5.1 “System data AC500-eCo V3”
on page 925
Only additional details are therefore documented below.
Parameter Value
Process supply voltage UP
Connections Terminal 6 for UP (+24 V DC) and terminal 7
for ZP (0 V DC)
Rated value 24 V DC
Current consumption via UP terminal 5 mA + max. 0.5 A per output
Max. ripple 5 %
Inrush current
0.000002 A
2
s
Protection against reversed voltage Yes
Rated protection fuse for UP On request
Current consumption from 24 V DC power
supply at the L+/M terminals of the CPU
Ca. 10 mA
Galvanic isolation Yes, between the output group and the rest of
the module
Isolated groups 1 (4 channels per group)
Surge-voltage (max.) 35 V DC for 0.5 s
Max. power dissipation within the module 0.5 W
Weight 16 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
Table 28: Technical data of the digital outputs
Parameter Value
Number of channels per module 4 transistor outputs (24 V DC, 0.5 A max.)
Distribution of the channels into groups 1 (4 channels per group)
Connection of the channels O0 to O3 Terminals 2 to 5
State LEDs
Technical data
Device specifications
Processor modules > AC500-eCo
2022/01/313ADR010278, 3, en_US62

Table of Contents