EasyManua.ls Logo

ABB AC500 V3 - Page 69

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The system data of AC500-eCo V3 apply
Ä
Chapter 2.5.1 “System data AC500-eCo V3”
on page 925
Only additional details are therefore documented below.
Parameter Value
Process supply voltage UP
Connections Terminal 6 for UP (+24 V DC) and ter-
minal 7 for ZP (0 V DC)
Rated value 24 V DC
Current consumption via UP terminal 5 mA + max. 0.5 A per output
Max. ripple 5 %
Inrush current 0.000002 A²s
Protection against reversed voltage Yes
Rated protection fuse for UP On request
Current consumption from 24 V DC power supply
at the L+/M terminals of the CPU
Ca. 10 mA
Galvanic isolation Yes, between the input group and the
output group and the rest of the module
Isolated groups 2 groups (1 group for 2 input channels, 1
group for 2 output channels)
Surge-voltage (max.) 35 V DC for 0.5 s
Max. power dissipation within the module 0.7 W
Weight 15 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not
be hindered by cable ducts or other parts
in the switchgear cabinet.
Table 31: Technical data of the digital inputs
Parameter Value
Number of channels per module 2
Distribution of the channels into groups 1 group for 2 channels
Connections of the channels I0 to I1 Terminals 2 to 3
Reference potential for the channels I0 to I1 Terminal 1
Indication of the input signals 1 yellow LED per channel; the
LED is ON when the input signal
is high (signal 1)
Monitoring point of input indicator LED
It is not part of input circuit (its
controlled by processor side, not
process side)
Input type according to EN 61131-2 Type 1 source Type 1 sink
Input signal range -24 V DC +24 V DC
Signal 0 -5 V...+3 V -3 V...+5 V
Technical data
Device specifications
Processor modules > AC500-eCo
2022/01/31 3ADR010278, 3, en_US 69