EasyManua.ls Logo

ABB AC500 - Page 87

ABB AC500
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
____________________________________________________________________________________________________________
G1 Introduction to AC500 1-85 AC500 / Issued: 07.2006
The I/Os will have the following CPU addresses in the CPU mapping table:
Channels Address in
the mapping /
programming
software
Comment
Digital inputs 0-15 %IW0 All the 16 digital inputs combined as Word from the
DC532 module
Digital inputs 0-7 %IB0 All the 8 first digital inputs combined as Byte
Digital inputs 8-15 %IB1 All the 8 following digital inputs combined as Byte
Single digital input 0
to
single digital input 7
%IX0.0
to
%IX0.7
Single digital input as a bit for the input 0 to the input 7
Single digital input 8
to
single digital input 15
%IX1.0
to
%IX1.7
Single digital input as a bit for the input 8 to the input 15
Digital configurable
inputs 16-31
%IW1 All the 16 digital configurable I/Os as inputs in combined
as Word from the DC532 module
Digital configurable
inputs 16-23
%IB2 All the 8 following digital configurable I/Os as inputs
combined as Byte
Digital configurable
inputs 24-31
%IB3 All the 8 following digital configurable I/Os as inputs
combined as Byte
Single digital
configurable input 16
to
single digital
configurable input 23
%IX2.0
to
%IX2.7
Single digital configurable I/Os as input as a bit for the
input 16 to the input 23
Single digital
configurable input 24
to
single digital
configurable input 31
%IX3.0
to
%IX3.7
Single digital configurable I/Os as input as a bit for the
input 24 to the input 31
Digital configurable
outputs 16-31
%QW0 All the 16 digital configurable I/Os as outputs combined
as Word from the DC532 module
Digital configurable
outputs 16-23
%QB0 All the 8 following digital configurable I/Os as outputs
combined as Byte
Digital configurable
outputs 24-31
%QB1 All the 8 following digital configurable I/Os as outputs
combined as Byte
Single digital
configurable output 16
to
single digital
configurable output 23
%QX0.0
to
%QX0.7
Single digital configurable I/Os as output as a bit for the
output 16 to the output 23
Single digital
configurable output 24
to
single digital
configurable output 31
%QX1.0
to
%QX1.7
Single digital configurable I/Os as output as a bit for the
output 24 to the output 31
For more details concerning the I/O mapping, please refer to the AC500 User's manual.