the derated current. Multiply the drive output current with the applicable derating factor
from the table.
Derating is not necessary when changing parameter 97.01 Switching frequency
reference.
Frame R4: If the application is cyclic and the surrounding air temperature is constantly
over 40 °C (104 °F), keep parameter 97.02 Minimum switching frequency at its default
value (1.5 kHz). Higher switching frequencies decrease the product life time or the
performance in the temperature range 40 60°C (104 140 °F).
Derating factorIEC type
ACH480-
04-…
12 kHz8 kHz< 4 kHz
3-phase U
N
= 400 V
0.480.651.002A7-4
0.480.651.003A4-4
0.480.651.004A1-4
0.480.651.005A7-4
0.480.651.007A3-4
0.480.651.009A5-4
0.510.681.012A7-4
0.510.681.0018A-4
0.510.671.0026A-4
0.490.651.0033A-4
0.490.651.0039A-4
0.490.661.0046A-4
0.490.661.0050A-4
Derating factorUL (NEC)
type
ACH480-
04-…
12 kHz8 kHz< 4 kHz
3-phase U
N
= 480 V
0.480.651.002A1-4
0.480.651.003A0-4
0.480.651.003A5-4
0.480.651.004A8-4
0.480.651.006A0-4
0.480.651.007A6-4
0.510.681.0011A-4
0.510.681.0014A-4
0.510.671.0021A-4
0.490.651.0027A-4
Technical data 129