ABB ACH480 Series - Terminal Data for the Power Cables

ABB ACH480 Series
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Frame
Cable conductor sizes (mm
2
)
1)
IEC type
ACH480-
04-…
R43×25 + 16050A-4
1)
Size of typical power cable (symmetrical, shielded, three-phase copper cable). Note that for the input power
connection, you may have to use two separate PE conductors (IEC 61800-5-1).
FrameWire size, Cu (AWG)UL (NEC)
type
ACH480-
04-…
3-phase U
N
= 480 V
R11602A1-4
R11603A0-4
R11603A5-4
R11604A8-4
R11606A0-4
R11407A6-4
R214011A-4
R310014A-4
R310021A-4
R48027A-4
R46034A-4
R44042A-4
Terminal data for the power cables
PE
L1, L2, L3, T1/U, T2/V, T3/W, R-, R+/
UDC+
IEC type
ACH480-
04-…
Tightening
torque
Maximum
(solid/stran-
ded)
Minimum
(solid/stran-
ded)
Tightening
torque
Maximum
(solid/stran-
ded)
Minimum
(solid/stran-
ded)
N·mmm
2
mm
2
N·mmm
2
mm
2
3-phase U
N
= 400 V
1.26/44/2.50.5…0.64/2.50.5/0.502A7-4
1.26/44/2.50.5…0.64/2.50.5/0.503A4-4
1.26/44/2.50.5…0.64/2.50.5/0.504A1-4
1.26/44/2.50.5…0.64/2.50.5/0.505A7-4
1.26/44/2.50.5…0.64/2.50.5/0.507A3-4
1.26/44/2.50.5…0.64/2.50.5/0.509A5-4
1.26/44/2.50.5…0.64/2.50.5/0.512A7-4
1.26/44/2.51.2…1.510/60.5/0.5018A-4
140 Technical data