Def /
FbEq16/32
DescriptionName/ValueNo.
-1 = Relay output 4 is ON.Bit 0 RO4
-1 = Relay output 5 is ON.Bit 1 RO5
-1 = Relay output 6 is ON.Bit 2 RO6
-1 = Relay output 7 is ON.Bit 3 RO7
1 = 1The electrical statuses of the relay/digital outputs can
be overridden for e.g. testing purposes. A bit in
parameter 15.06 RO forced data is provided for each
relay or digital output, and its value is applied whenever
the corresponding bit in this parameter is 1.
RO force selection15.05
-1 = Force relay output 4 to value of bit 0 of parameter
15.06 RO forced data.
Bit 0 RO4
-1 = Force relay output 5 to value of bit 0 of parameter
15.06 RO forced data.
Bit 1 RO5
-1 = Force relay output 6 to value of bit 0 of parameter
15.06 RO forced data.
Bit 2 RO6
-1 = Force relay output 7 to value of bit 0 of parameter
15.06 RO forced data.
Bit 3 RO7
1 = 1Allows the data value of a forced relay or digital output
to be changed from 0 to 3.
RO forced data15.06
-Force the value of this bit to RO4, if so defined in
parameter 15.05 RO force selection.
Bit 0 RO4
-Force the value of this bit to RO5, if so defined in
parameter 15.05 RO force selection.
Bit 1 RO5
-Force the value of this bit to RO6, if so defined in
parameter 15.05 RO force selection.
Bit 2 RO6
-Force the value of this bit to RO7, if so defined in
parameter 15.05 RO force selection.
Bit 3 RO7
Not
energized
Selects a drive signal to be connected to relay output
RO4.
RO4 source15.07
0Output is not energized.Not energized
1Output is energized.Energized
…For the complete parameter list, refer to the drive firmware manual.
0.0 sDefines the activation delay for relay output RO4.RO4 ON delay15.08
10 = 1 sActivation delay for RO4.0.0 … 3000.0 s
0.0 sDefines the deactivation delay for relay output RO4.RO4 OFF delay15.09
10 = 1 sDeactivation delay for RO4.0.0 … 3000.0 s
Not
energized
Selects a drive signal to be connected to relay output
RO5.
RO5 source15.10
0Output is not energized.Not energized
1Output is energized.Energized
…For the complete parameter list, refer to the drive firmware manual.
0.0 sDefines the activation delay for relay output RO5.RO5 ON delay15.11
210 BREL-01 relay output extension module