Connection procedure
WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or death,
or damage to the equipment can occur. If you are not a qualified electrical
professional, do not do installation, commissioning or maintenance work.
Refer to Terminal data for the power cables (page 163) for the tightening torques.
1. Do the steps in section Electrical safety precautions (page 18) before you start
the work.
2. Install the conduits, and attach them to the cable entry plate of the enclosure
that the drive is installed in.
3. Make sure that the conduit is correctly grounded at the cable entry.
4. Strip the conductor ends and pull the conductors through the conduits.
5. Remove the screw on the drive front cover, then lift the front cover up.
6. Attach the residual voltage warning sticker in the local language to the drive.
7. Connect the protective earth (ground) conductor of the motor wiring to the
grounding terminal.
100 Electrical installation – North America