52 E-Clipse Bypass Configurations for ACH550 Drives
Parameter Descriptions
Group 03
Code Name Resolution Range Default Description
0306 FLT WORD 2 — b0: 1 = Motor Underload
b1: 1 = Max cycling fault
b2: 1 = Drive link fault
b3: 1 = Reverse rotation
b4: 1 = Phase A current
measurement
b5: 1 = Phase C current
measurement
b6: 1 = Bypass coil shorted
b7: 1 = Drive coil shorted
b8: not used
b9: not used
b10: 1 = Invalid sub-
assembly
b11: 1 = Serial 1 Err
b12: 1 = EFB Config File
b13: 1 = Force Trip
b14: 1 = EFB 1
b15: 1 = EFB 2
0 Bypass fault status, word 2
0307 FLT WORD 3 — b0: 1 = EFB 3
b1: 1 = Open motor phase
b2: not used
b3: not used
b4: 1 = Control board
temperature
b5: not used
b6: not used
b7: not used
b8: 1 = RBIO ID error
b9: 1 = Stack overflow
b10: 1 = Timed scan
overflow
b11: 1 = Serial flash corrupt
b12: 1 = Unknown drive
b13: 1 = Unknown bypass
b14 - b15: not used
0 Bypass fault status, word 3
0308 ALR WORD 1 — b0: 1 = Input phase A loss
b1: 1 = Input phase B loss
b2: 1 = Input phase C loss
b3: 1 = Auto transfer active
b4: 1 = External Comm
Error
b5: 1 = Run Enable
b6: 1 = PCB Temp
b7: 1 = Drive Setup
b8: 1 = Bypass run delay
b9: 1 = Motor Temp
b10: 1 = Underload
b11: 1 = Bypass disabled
b12: 1 = Drive link error
b13: 1 = Drive test
b14: 1 = Drive 1st start
needed
b15: 1 = Low input voltage
0 Bypass alarm status, word 1