E-Clipse Bypass Configurations for ACH550 Drives 57
Parameter Descriptions
Group 14
Code Name Resolution Range Default Description
1411 R4 ON DLY 0.1 sec 0-3600.0s 0s Delay from active state to active
output.
1412 R4 OFF DLY 0.1 sec 0-3600.0s 0s Delay from inactive state to
inactive output.
1413 RO5 SELECT 1 See RO 1 Select. BYPASS
AUTO
(13)
1414 R5 ON DLY 0.1 sec 0-3600.0s 0s Delay from active state to active
output.
1415 R5 OFF DLY 0.1 sec 0-3600.0s 0s Delay from inactive state to
inactive output.
Group 16
Code Name Resolution Range Default Description
1601 START/STOP 1 0 = NOT SEL
1 = DI1
2 = COMM
DI 1
(1)
Selects source for system start
command.
1602 RUN
ENABLE
10 = NOT SEL
1 = DI2
2 = COMM
NOT SEL
(0)
Selects source for run enable
command.
1603 START EN 1 1 0 = NOT SEL
1 = DI3
2 = COMM
DI 3
(1)
Selects source for start enable 1
command.
1604 START EN 2 1 0 = NOT SEL
1 = DI4
2 = COMM
NOT SEL
(0)
Selects source for start enable 2
command.
1605 START EN 3 1 0 = NOT SEL
1 = DI5
2 = COMM
NOT SEL
(0)
Selects source for start enable 3
command.
1606 START EN 4 1 0 = NOT SEL
1 = DI2
2 = COMM
NOT SEL
(0)
Selects source for start enable 4
command.
1607 RESET SRC 1 0 = NOT SEL
1 = DI4
2 = COMM
NOT SEL
(0)
Selects source for fault reset
command (rising edge).

Table of Contents