58 E-Clipse Bypass Configurations for ACH550 Drives
Parameter Descriptions
Group 16
Code Name Resolution Range Default Description
1608 AUTO XFR 1 0 = NOT SEL
1 = ENABLE
NOT SEL
(0)
Enabled allows auto transfer to
bypass on all drive faults except
the conditional faults which
require an additional enable.
NOT SEL prevents auto transfer
to bypass for all drive faults
including the conditional faults.
1609 OC
TRANSFR
10 = NOT SEL
1 = ENABLE
NOT SEL
(0)
Drive over current causes auto
transfer. Requires global auto
transfer enable also.
1610 OV
TRANSFR
10 = NOT SEL
1 = ENABLE
NOT SEL
(0)
Drive over voltage causes auto
transfer. Requires global auto
transfer enable also.
1611 UV
TRANSFR
10 = NOT SEL
1 = ENABLE
NOT SEL
(0)
Drive under voltage causes auto
transfer. Requires global auto
transfer enable also.
1612 AI TRANSFR 1 0 = NOT SEL
1 = ENABLE
NOT SEL
(0)
Drive AI loss causes auto
transfer. Requires global auto
transfer enable also.
1613 BP DISABLE 1 0 = NOT SEL
1 = DISABLE
NOT SEL
(0)
Disables bypass mode.
1614 BP RUN DLY 1 sec 0 - 300 secs 0s Bypass contactor pick-up delay
when starting bypass or
transferring from Drive mode.
1615 SAVE
PARAM
10 = DONE
1 = SAVE
0 Save User Settings (SaveImm +
SavePwrd).
1616 DISP ALRMS 1 0 = DISABLE
1 = ENABLE
ENABLE
(1)
Enables alarms to be displayed:
INP PHASE A LOSS,
INP PHASE B LOSS,
INP PHASE C LOSS,
MTR OVERLOAD,
BYPASS DISABLED,
DRIVE SETUP,
PCB TEMP
DRIVE LINK ERROR
DRIVE FAULTED
1617 DRIVE TEST 1 0 = DISABLE
1 = ENABLE
DISABLE
(0)
Enables drive test mode. Drive
contactor is opened.
1618 PASS CODE 1 0 - 65535 0 Enter correct password to here in
order to change value of the PAR
LOCK. Default password value is
"123".