90 E-Clipse Bypass Configurations for ACH550 Drives
Technical Data
Vertical Enclosure Terminals, 208…240 Volt Units
Vertical Enclosure Terminals, 380…480 Volt Units
208…240 Volt
Frame
Size
Maximum Wire Size Capacities of Power Terminals
HP Identification
Circuit
Breaker
Disconnect
Switch
Motor
Termination
Ground
Lugs
1 ACH550-VxR-04A6-2 R1
#10
35 in-lbs
#10
7 in-lbs
#6
30 in-lbs
#4
35 in-lbs
1.5 ACH550-VxR-06A6-2 R1
2 ACH550-VxR-07A5-2 R1
3 ACH550-VxR-012A-2 R1
5 ACH550-VxR-017A-2 R1
7.5 ACH550-VxR-024A-2 R2
#8
40 in-lbs
#8
7 in-lbs
10 ACH550-VxR-031A-2 R2
#2
50 in-lbs
#2
50 in-lbs
#2
50 in-lbs
15 ACH550-VxR-046A-2 R3
#4
18 in-lbs
#2/0
120 in-lbs
20 ACH550-VxR-059A-2 R3
25 ACH550-VxR-075A-2 R4
#1
50 in-lbs
#1
55 in-lbs
380…480 Volt
Frame
Size
Maximum Wire Size Capacities of Power Terminals
HP Identification
Circuit
Breaker
Disconnect
Switch
Motor
Termination
Ground
Lugs
1/1.5 ACH550-VxR-03A3-4 R1
#10
35 in-lbs
#10
7 in-lbs
#6
30 in-lbs
#4
35 in-lbs
2 ACH550-VxR-04A1-4 R1
3 ACH550-VxR-06A9-4 R1
5 ACH550-VxR-08A8-4 R1
7.5 ACH550-VxR-012A-4 R1
10 ACH550-VxR-015A-4 R2
#8
40 in-lbs
#8
7 in-lbs
15 ACH550-VxR-023A-4 R2
20 ACH550-VxR-031A-4 R3
#3
50 in-lbs
#2
50 in-lbs
#2
50 in-lbs
25 ACH550-VxR-038A-4 R3
#4
18 in-lbs
30 ACH550-VxR-045A-4 R3
40 ACH550-VxR-059A-4 R4
#1
50 in-lbs
#2/0
120 in-lbs
50 ACH550-VxR-072A-4 R4
#1
55 in-lbs
60 ACH550-VxR-078A-4 R4
#1
70 in
-lbs