EasyManua.ls Logo

ABB ACH550-VCR - Page 229

ABB ACH550-VCR
642 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACH550-UH User’s Manual 1-225
Embedded fieldbus
63 EXT PID FBCK The External PID feedback signal. 0131
64 EXT PID DEV The deviation of the External PID output signal from its
setpoint.
0133
65 N/A
66 SPD OUT MIN Sets the minimum output speed of the drive as a percentage
of the motor nominal rating.
2007
(SCALAR)
2001
(SPEED)
67 SPD OUT MAX Sets the maximum output speed of the drive as a percentage
of the motor nominal rating.
2008
(SCALAR)
2002
(SPEED)
68 FLN LOC CTL Commanded by FLN to temporarily “steal” start/stop control
of the drive from its normal source and place it under FLN
control. This functionality is analogous to placing the drive in
HAND mode at the panel, with the control being taken by
FLN instead. HAND mode at the panel has priority over this
point. Thus, this point is only effective in temporarily taking
control from the digital inputs or some other internal control
functionality.
69 FLN LOC REF Commanded by FLN to temporarily “steal” input reference
control of the drive from its normal source and place it under
FLN control. This functionality is analogous to placing the
drive in HAND mode at the panel, with the reference control
being taken by FLN instead. HAND mode at the panel has
priority over this point. Thus, this point is only effective in
temporarily taking control from the analog inputs or some
other internal control functionality.
70 DI 1 ACTUAL Indicates the status of Digital Input 1 (1 = ON, 0 = OFF). 0118, bit 2
71 DI 2 ACTUAL Indicates the status of Digital Input 2 (1 = ON, 0 = OFF). 0118, bit 1
72 DI 3 ACTUAL Indicates the status of Digital Input 3 (1 = ON, 0 = OFF). 0118, bit 0
73 DI 4 ACTUAL Indicates the status of Digital Input 4 (1 = ON, 0 = OFF). 0119, bit 2
74 DI 5 ACTUAL Indicates the status of Digital Input 5 (1 = ON, 0 = OFF). 0119, bit 1
75 DI 6 ACTUAL Indicates the status of Digital Input 6 (1 = ON, 0 = OFF). 0119, bit 0
76 RO 1 ACTUAL Indicates the status of Relay Output 1 (1 = ON, 0 = OFF). 0122, bit 2
77 RO 2 ACTUAL Indicates the status of Relay Output 2 (1 = ON, 0 = OFF). 0122, bit 1
78 RO 3 ACTUAL Indicates the status of Relay Output 3 (1 = ON, 0 = OFF). 0122, bit 0
79 RO 4 ACTUAL Indicates the status of Relay Output 4 (1 = ON, 0 = OFF). 0123, bit 2
80 RO 5 ACTUAL Indicates the status of Relay Output 5 (1 = ON, 0 = OFF). 0123, bit 1
81 RO 6 ACTUAL Indicates the status of Relay Output 6 (1 = ON, 0 = OFF). 0123, bit 0
82 AI 1 ACTUAL Indicates the input level of Analog Input 1. 0120
83 AI 2 ACTUAL Indicates the input level of Analog Input 2. 0121
84 AO 1 ACTUAL Indicates the output level of Analog Output 1. 0124
85 AO 2 ACTUAL Indicates the output level of Analog Output 2. 0125
FLN Detailed Point Descriptions
Point Description
Drive
Parameter

Table of Contents

Other manuals for ABB ACH550-VCR

Related product manuals