1-226 ACH550-UH User’s Manual
Embedded fieldbus
86 OK.ALARM Indicates the current alarm state of the drive
(1 = ALARM, 0 = OK).
87 OK.MAINT Indicates the current maintenance state of the drive
(1 = MAINT, 0 = OK).
Maintenance triggers are configured in drive parameter
Group 29.
88 ALARM WORD1 This point is a bit-field indicating active alarms in the drive. 0308
89 ALARM WORD2 This point is a bit-field indicating active alarms in the drive. 0309
90 LAST FAULT This point is first in the drive's fault log and indicates the most
recent fault declared.
0401
91 PREV FAULT 1 This point is second in the drive's fault log and indicates the
previous fault declared.
0412
92 PREV FAULT 2 This point is last in the drive's fault log and indicates the
oldest fault in the log.
0413
93 OK.FAULT Indicates the current fault state of the drive
(1 = FAULT, 0 = OK).
94 RESET FAULT Command by FLN to reset a faulted drive
(1 = RESET, 0 = NO).
Parameter 1604 must be set to COMM for FLN to control this
state.
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any need
for an explicit command to clear the point before a
subsequent reset can be issued.
95 MBOX PARAM Sets the parameter to be used by the mailbox function.
96 MBOX DATA Sets or indicates the data value of the mailbox function.
97 MBOX READ Command by FLN to read the parameter value specified by
Point 95, MBOX PARAM. The parameter value is returned in
Point 96, MBOX DATA.
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any need
for an explicit command to clear the point before a
subsequent reset can be issued.
98 MBOX WRITE Command by FLN to write the data value specified by Point
96, MBOX DATA, to the parameter value specified by Point
95, MBOX PARAM.
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any need
for an explicit command to clear the point before a
subsequent reset can be issued.
99 ERROR STATUS 1 of the 5 mandatory FLN points required for compatibility
with Siemens control systems. It has no functionality in the
drive application.
None
FLN Detailed Point Descriptions
Point Description
Drive
Parameter