ACH550 E-Clipse Bypass User’s Manual 2-77
Parameters
Group 51: External Comm Mode
Group 51: External Comm Mode
Code Name Resolution Range Default Description
5101 FBA TYPE 1 0 = NOT DEFINED
1 = Profibus
15 = LonWorks
32 = CANOpen
37 = DeviceNet
Displays type of attached
fieldbus adapter module.
5102
...
5126
FBA PAR 2
...
FBA PAR 26
1 0 - 65535 0 Fieldbus specific - consult FBA
Users Manual.
5127 REFRESH 1 0 = DONE
1 = REFRESH
0 Validates any changed adapter
module configuration
parameters. After refreshing,
value reverts automatically to
DONE.
5128 FBA PAR 28 1 0 - 0xFFFF 0 Parameter table version
5129 FBA PAR 29 1 0 - 0xFFFF 0 Bypass type code
5130 FBA PAR 30 1 0 - 0xFFFF 0 Mapping file version
5131 FBA PAR 31 1 0 - 6 0 Fieldbus adapter status
5132 FBA PAR 32 1 0 - 0xFFFF 0 Module common software
version
5133 FBA PAR 33 0 - 0xFFFF 0 Module application software
version