2-90 ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
5002 BP STATION ID
Defines the drives node
address of the EIA 485 link.
Set each bypass on the
network with a unique value for
this parameter.
When this protocol is selected,
the default value for this
parameter is: 256
Note: For a new address to
take affect, the system power
must be cycled OR 5002 must
first be set to 0 before selecting
a new address. Leaving 5002 =
0 places the EIA 485 channel
in reset, disabling
communication.
Sets MS/TP MAC ID. A
temporary value of 0
places the protocol
channel in reset.
Default: 129
5003 EFB BAUD RATE
Defines the communication
speed of the EIA 485 link in
kbits per second (kbits/s).
1.2 kbits/s
2.4 kbits/s
4.8 kbits/s
9.6 kbits/s
19.2 kbits/s
38.4 kbits/s
57.6 kbits/s
76.8 kbits/s
(Read Only Copy, edit in 5303)
5004 EFB PARITY
Defines the data length,
parity and stop bits to be
used with the EIA 485 link
communication.
The same settings must
be used in all on-line
stations.
0 = 8
N1 – 8 data bits, No
parity, one stop bit.
1 = 8N2 – 8 data bits, No
parity, two stop bits.
2 = 8
E1 – 8 data bits, Even
parity, one stop bit.
3 = 8
O1 – 8 data bits, Odd
parity, one stop bit.
(Read Only Copy, edit in 5304)
Bypass
Parameter
Description
EFB Protocol Reference
Modbus N2 FLN BACnet

Table of Contents