2-90 ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
5002 BP STATION ID
Defines the drives node
address of the EIA 485 link.
Set each bypass on the
network with a unique value for
this parameter.
When this protocol is selected,
the default value for this
parameter is: 256
Note: For a new address to
take affect, the system power
must be cycled OR 5002 must
first be set to 0 before selecting
a new address. Leaving 5002 =
0 places the EIA 485 channel
in reset, disabling
communication.
Sets MS/TP MAC ID. A
temporary value of 0
places the protocol
channel in reset.
Default: 129
5003 EFB BAUD RATE
Defines the communication
speed of the EIA 485 link in
kbits per second (kbits/s).
1.2 kbits/s
2.4 kbits/s
4.8 kbits/s
9.6 kbits/s
19.2 kbits/s
38.4 kbits/s
57.6 kbits/s
76.8 kbits/s
(Read Only Copy, edit in 5303)
5004 EFB PARITY
Defines the data length,
parity and stop bits to be
used with the EIA 485 link
communication.
• The same settings must
be used in all on-line
stations.
0 = 8
N1 – 8 data bits, No
parity, one stop bit.
1 = 8N2 – 8 data bits, No
parity, two stop bits.
2 = 8
E1 – 8 data bits, Even
parity, one stop bit.
3 = 8
O1 – 8 data bits, Odd
parity, one stop bit.
(Read Only Copy, edit in 5304)
Bypass
Parameter
Description
EFB Protocol Reference
Modbus N2 FLN BACnet