2-114 ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
N2 analog output objects – drive
The following table lists the N2 Analog Output objects defined for the ACH550 drive.
BI20 DRIVE READY Status Word 0 = Not Ready, 1 = Ready
BI21 AT SETPOINT Status Word 0 = No, 1 = At Setpoint
BI22 RUN ENABLED Status Word 0 = Not Enabled, 1 = Enabled
BI23 N2 LOCAL MODE Status Word 0 = Auto, 1 = N2 Local
BI24 N2 CONTROL SRC Status Word 0 = No, 1 = Yes
BI25 N2 REF1 SRC Status Word 0 = No, 1 = Yes
BI26 N2 REF2 SRC Status Word 0 = No, 1 = Yes
N2 Analog Outputs:
Number Object
Drive
Parameter
Scale
Factor
Units Range
AO1 REFERENCE 1 Reference 1 10 % 0…100
AO2 REFERENCE 2 Reference 2 10 % 0…100
AO3 ACCEL TIME 1 2202 10 s 0.1…1800
AO4 DECEL TIME 1 2203 10 s 0.1…1800
AO5 CURRENT LIMIT 2003 10 A 0…1.3•I
2n
AO6 PID1-CONT GAIN 4001 10 % 0.1…100
AO7 PID1-CONT I-TIME 4002 10 s 0.1…600
AO8 PID1-CONT D-TIME 4003 10 s 0…10
AO9 PID1-CONT D FILTER 4004 10 s 0…10
AO10 PID2-CONT GAIN 4101 10 % 0.1…100
AO11 PID2-CONT I-TIME 4102 10 s 0.1…600
AO12 PID2-CONT D-TIME 4103 10 s 0…10
AO13 PID2-CONT D FILTER 4104 10 s 0…10
AO14 COMMAND AO 1 135 10 % 0…100
AO15 COMMAND AO 2 136 10 % 0…100
AO16 EXT PID SETPOINT 4211 10 % 0…100
AO17 SPD OUT MIN 2001/2007 10 % 0…200
AO18 SPD OUT MAX 2002/2008 10 % 0…200
AO19 MAILBOX PARAMETER 1 0…65535
AO20 MAILBOX DATA 1 0…65535
N2 Binary Inputs:
Number Object Drive Parameter Range