ACH550 E-Clipse Bypass User’s Manual 2-119
Embedded fieldbus
N2 analog output objects – bypass
The following table lists the N2 Analog Input objects defined for the ABB E-Clipse
bypass.
N2 binary input objects – bypass
The following table lists the N2 Binary Input objects defined for the ABB E-Clipse
bypass.
AI4 ALARM WORD 2 0309 1 Alarm mask
(see bypass
manual
description of
parameter
0309)
AI5 HAND OFF AUTO 0=Off, 1=Hand,
2=Auto
AI6 INPUT VOLT 0102 1 V Average of line-
line input
voltage
AI7 PCB TEMP 0105 0.1
°C Temperature of
bypass board
AI8 KW HOURS 0106 1 kWh Bypass-mode
kilowatt hours
AI9 RUN TIME 0108 1 HR 0...65535
AI10 A-B VOLT 0111 1 V Phase A -
Phase B voltage
AI11 B-C VOLT 0112 1 V Phase B -
Phase C voltage
AI12 C-B VOLT 0113 1 V Phase C -
Phase A voltage
N2 Analog Inputs:
Number Object
Bypass
Parameter
Scale
Factor
Units Range
AO1 BYP RUNDLY 1614 1 s 0…300
AO2 MB PARAM NA 1 None 0…65535
AO3 MB DATA NA 1 None 0…65535
N2 Binary Inputs:
Number Object Drive Parameter Range
BI1 SYSTEM READY Status Word 1 = Ready
BI2 SYSTEM ENABLED Status Word 1 = Enabled
BI3 SYSTEM STARTED Status Word 1 = System Started
BI4 SYSTEM RUNNING Status Word 1 = System Running
BI5 N2 LOCAL MODE Status Word 1 = N2 Local
N2 Analog Inputs:
Number Object
Bypass
Parameter
Scale
Factor
Units Range