2-120 ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
N2 binary output objects – bypass
The following table lists the N2 Binary Output objects defined for the ABB E-Clipse
bypass.
BI6 FAULT Status Word 1 = Bypass Fault
BI7 ALARM Status Word 1 = Bypass Alarm
BI8 N2 CONTROL SCR Status Word 1 = Yes
BI9 OVERRIDE Status Word 1 = Override
BI10 INPUT 1 STATUS 0103 (bit mask 1) 1 = On
BI11 INPUT 2 STATUS 0103 (bit mask 2) 1 = On
BI12 INPUT 3 STATUS 0103 (bit mask 4) 1 = On
BI13 INPUT 4 STATUS 0103 (bit mask 8) 1 = On
BI14 INPUT 5 STATUS 0103 (bit mask 10h) 1 = On
BI15 INPUT 6 STATUS 0103 (bit mask 20h) 1 = On
BI16 RELAY 1 STATUS 0104 (bit mask 1) 1 = On
BI17 RELAY 2 STATUS 0104 (bit mask 2) 1 = On
BI18 RELAY 3 STATUS 0104 (bit mask 4) 1 = On
BI19 RELAY 4 STATUS 0104 (bit mask 8) 1 = On
BI20 RELAY 5 STATUS 0104 (bit mask 10h) 1 = On
BI21 BYPASS MODE Status Word 0 = Drive mode, 1 = Bypass mode
BI22 SYS UNDERLOAD Status Word 1 = System Underload
BI23 SYS FAULT Status Word 1 = System Fault
BI24 BYPASS RUNNING Status Word 1 = Bypass Running
N2 Binary Outputs:
Number Object Drive Parameter Range
BO1 SYSTEM START Command Word 1 = Started
BO2 SYSTEM ENABLE Command Word 1 = Enable
BO3 SYSTEM RESET Command Word Change 0 -> 1 Resets
BO4 OVERRIDE Command Word 1 = Override
BO5 COMMAND RO 1 107 (bit mask 1) 1 = On
BO6 COMMAND RO 2 107 (bit mask 2) 1 = On
BO7 COMMAND RO 3 107 (bit mask 4) 1 = On
BO8 COMMAND RO 4 107 (bit mask 8) 1 = On
BO9 COMMAND RO 5 107 (bit mask 10h) 1 = On
BO10 SYSTEM ENABLE 1 Command Word 1 = Enable
BO11 SYSTEM ENABLE 2 Command Word 1 = Enable
BO12 SYSTEM ENABLE 3 Command Word 1 = Enable
BO13 SYSTEM ENABLE 4 Command Word 1 = Enable
N2 Binary Inputs:
Number Object Drive Parameter Range