ACH550 E-Clipse Bypass User’s Manual 2-147
Embedded fieldbus
94 RESET FAULT This point is commanded by FLN to reset a faulted bypass
(1 = RESET, 0 = NO). Bypass parameter 1607 must be set
to COMM for FLN to control this state. This point is
“momentary”, i.e. it will automatically return to its inactive
state once the command is issued. This is a convenience
for the user, since this control input is rising-edge sensitive
and would otherwise require an explicit command to clear it
before a subsequent reset could be issued.
99 ERROR STATUS This is 1 of 5 mandatory FLN points required for
compatibility with Siemens control systems. It has no
functionality in the bypass application.
FLN Detailed Point Descriptions