1-84 ACH550-UH User’s Manual
Parameters
0130 PID 1 FBK Unit and scale defined - -
by par. 4006/4106 and
4007/4107
The
PID 1 controller feedback signal.
Units and scale defined by PID parameters.
0131 PID 2 FBK Unit and scale defined - -
by par. 4206 and 4207
The
PID 2 controller feedback signal.
Units and scale defined by PID parameters.
0132 PID 1 DEVIATION Unit and scale defined - -
by par. 4006/4106 and
4007/4107
The difference between the
PID 1 controller reference value and actual value.
Units and scale defined by PID parameters.
0133 PID 2 DEVIATION Unit and scale defined - -
by par. 4206 and 4207
The difference between the
PID 2 controller reference value and actual value.
Units and scale defined by PID parameters.
0134 COMM RO WORD 0…65535 1 -
Free data location that can be written from serial link.
Used for relay output control.
See parameter 1401.
0135 COMM VALUE 1 -32768…+32767 1 -
Free data location that can be written from serial link.
0136 COMM VALUE 2 -32768…+32767 1 -
Free data location that can be written from serial link.
0137 PROCESS VAR 1 - 1 -
Process variable 1
Defined by parameters in Group 34: PANEL DISPLAY.
0138 PROCESS VAR 2 - 1 -
Process variable 2
Defined by parameters in Group 34: PANEL DISPLAY.
0139 PROCESS VAR 3 - 1 -
Process variable 3
Defined by parameters in Group 34: PANEL DISPLAY.
0140 RUN TIME 0.00…499.99 kh 0.01 kh -
The drive’s accumulated running time in thousands of hours (kh).
Cannot be reset.
0141 MWH COUNTER 0…65535 MWh 1 MWh -
The drive’s accumulated power consumption in megawatt hours.
The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0.
Cannot be reset.
0142 REVOLUTION CNTR 0…65535 Mrev 1 Mrev -
The motor’s accumulated revolutions in millions of revolutions.
Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0143 DRIVE ON TIME HI 0…65535 days 1 day -
The drive’s accumulated power-on time in days.
Cannot be reset.
Group 01: Operating Data