1. Switch off the power from the drive.
2.
Open the cover, if not already opened. Frame R4: see page 174, frame R5: see page
178, frames R6…R9: see page 182.
3. To disconnect the internal EMC filters:
The DC EMC filter is disconnected by default with a plastic screw (3a).
The AC EMC filter is disconnected by default with a plastic screw (3b).
4. To disconnect the ground-to-phase varistor, replace the metal varistor screw (4)
with the plastic screw provided in the package, or just remove the metal screw.
R5R4
R6…R9
Default materialScrew
PlasticEMC (DC)A
PlasticEMC (AC)B
MetalVARC
Electrical installation – North America 171