Reference resistor typesP
BRmax
R
max
R
min
ACH580-01-
kWohmohm
Built in with the brake chopper5110.77.8078A-4
SAFUR125F500638.71.3096A-4
SAFUR125F500777.11.3124A-4
SAFUR200F5001055.21.3156A-4
SAFUR200F5001264.31.3180A-4
2xSAFUR125F5001563.51.3240A-4
2xSAFUR210F5751872.91.3260A-4
----302A-4
2xSAFUR200F5002272.40.7361A-4
2xSAFUR200F5002841.90.7414A-4
3-phase U
1
= 525…600 V, P
n
at U
n
= 575 V
SAFUR90F57531306.5041A-6
SAFUR90F57543216.5052A-6
SAFUR90F57553176.5062A-6
SAFUR90F57564146.5077A-6
SAFUR80F5007811.54.3099A-6
SAFUR80F5001078.54.3125A-6
SAFUR80F50012873.2144A-6
SAFUR125F5001575.82.2192A-6
2xSAFUR200F5001884.82.2242A-6
2xSAFUR200F50022842.2271A-6
Symbols
= minimum allowed brake resistor that can be connected to the brake chopperR
min
= maximum allowed brake resistor that allows P
BRmax
R
max
= maximum braking capacity of the drive, must exceed the desired braking power.P
BRmax
WARNING!
Do not use a brake resistor with a resistance below the minimum value specified
for the particular drive. The drive and the internal chopper are not able to handle
the overcurrent caused by the low resistance.
■ Parameter settings for external braking chopper and resistor
Disable the overvoltage control of the drive with parameter 30.30 Overvoltage control.
Disable parameter 43.06 Braking chopper function as parameter group 43 Brake chopper
is used for internal braking chopper and resistor only.
Resistor braking 345