Technical data
Into slot 2 of drive control unitInstallation
IP20 / UL Type 1Degree of protection
See the drive technical data.Ambient conditions
CardboardPackage
Analog inputs (80..82, 83..85, 86..88)
1.5 mm
2
Maximum wire size
-11 V +11 VInput voltage ( AI+ and AI-)
-22 mA +22 mAInput current ( AI+ and AI-)
>200 kohm (voltage mode), 100 ohm (current
mode)
Input resistance
Optional cable shield connections
Analog outputs (90..92, 93..95)
1.5 mm
2
Maximum wire size
0 V +11 VOutput voltage (AO+ and AO-)
0 mA +22 mAOutput current (AO+ and AO-)
< 20 ohmOutput resistance
>10 kohmRecommended load
± 1% Typical, ± 1.5% Max of full-scale valueInaccuracy
Optional cable shield connections
Isolation areas
364 Optional I/O extension modules
Isolation areas:
Analog inputs (80...82, 83...85)
Wire size max. 1.5 mm
2
Input voltage (AI+ and AI-): -10 V ... +10 V
Input resistance: > 200 kohm
Optional cable shield connection
Analog outputs (86...88, 89...91)
Wire size max. 1.5 mm
2
Output voltage (AO and AGND): 0 V ... 10 V
Output resistance: < 20 ohm
Recommended load: > 10 kohm
Inaccuracy: typical ± 1%, max. ± 1.5% of full scale
Optional cable shield connection
Analog output scale switch
ON state: 0.5 V ... 9.5 V range in use
OFF state: 0 V ... 10 V range in use
Symbol Description
1 Plugged to drive SLOT2
2 SWITCH
Reinforced insulation (IEC 61800-5-1:2007)
Functional insulation (IEC 61800-5-1:2007)
CAIO-01
1
AI3
AO3
AO4
AI5
AI4
Plugged to drive control unit SLOT 21
Reinforced insulation (IEC 61800-5-1:2007)
372 Optional I/O extension and adapter modules