Parameter setting example for digital output
This example shows how to make digital output DO1 of the extension module indicate
the reverse direction of rotation of the motor with a one-second delay.
SettingParameter
Digital output15.22 DO1 configuration
Reverse15.23 DO1 source
1 s15.24 DO1 ON delay
1 s15.25 DO1 OFF delay
Parameter setting example for frequency output
This example shows how to make digital output DO1 of the extension module indicate
the motor speed 0…1500 rpm with a frequency range of 0…10000 Hz.
SettingParameter
Frequency output15.22 DO1 configuration
01.01 Motor speed used15.33 Freq out 1 source
015.34 Freq out 1 src min
1500.0015.35 Freq out 1 src max
1000 Hz15.36 Freq out 1 at src min
10000 Hz15.37 Freq out 1 at src max
Diagnostics
Faults and warning messages
Warning A7AB Extension I/O configuration failure.
LEDs
The extension module has one diagnostic LED.
DescriptionColor
The extension module is powered up.Green
■ Technical data
Into an option slot on the drive control unitInstallation
IP20 / UL Type 1Degree of protection
See the drive technical data.Ambient conditions
382 Optional I/O extension and adapter modules