EasyManua.ls Logo

ABB ACH580-01 - Requirements Table

ABB ACH580-01
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
the attenuation and reflection properties of the motor cable and the terminals. This can
cause additional stress on the motor and motor cable insulation.
Modern variable speed drives with their fast rising voltage pulses and high switching
frequencies can generate current pulses that flow through the motor bearings. This can
gradually erode the bearing races and rolling elements.
du/dt filters protect motor insulation system and reduce bearing currents. Common mode
filters mainly reduce bearing currents. Insulated N-end (non-drive end) bearings protect
the motor bearings.
Requirements table
These tables show how to select the motor insulation system and when a drive du/dt
and common mode filters and insulated N-end (non-drive end) motor bearings are
required. Ignoring the requirements or improper installation may shorten motor life or
damage the motor bearings and voids the warranty.
Guidelines for planning the electrical installation 89

Table of Contents

Other manuals for ABB ACH580-01

Related product manuals