ACH580 E-Clipse bypass and packaged drive user manual 99
Embedded fieldbus
5812
DV CRC
ERR
Rapidly
Increasing
Numeric
Value
1
1. Duplicate
Addresses
2. Too many devices
on wire
3. Noise on EIA-485
wire
1. See Corrective Action 1. Parameter
Number 5811
2. Limit to 31 unit loads on 1 segment
(Bypass = 1 unit load)
3. See Corrective Action 6. Parameter
Number 5811
5819
DV STATUS
IDLE 1. No network
connection
2. Blown EIA-485
transceiver
1. Land communication wires as shown in
drawings on page 78. Check Repeater (if
installed onsite)
2. See Corrective Action 7. Parameter
Number 5811
3. Change application number in the
Siemens field panel.
5813
5013
TOKEN CNT
(BACnet
Only)
Not
Increasing
Numeric
Value
1. Drive device
address parameter
5803 is set to 128 or
greater.
2. E-Clipse Bypass
device address
parameter 5003 is
set to 128 or greater.
3. Max Masters is set
too low on all drives.
1. Change parameter 5803 to a unique value
below 128.
2. Change parameter 5003 to a unique value
below 128.
Note: The default value for parameter
5003 is 256. This setting prevents the
network from seeing the bypass. Change
this setting ONLY if the bypass will be
seen as a node on the network.
3. Change Max Masters property at all
devices on bus to 127.
5808
DV OK MSG
OK
Message
Counter not
increasing
1
1. Master/Client not
communicating with
drive.
2. Failed router
1. Add device and points to the building
control system.
2. Replace router.
1) Reset by pressing UP and DOWN arrows simultaneously in edit mode. Save change by pressing
ENTER.
Parameter
Number
Display on
Panel
(Symptom)
Possible Cause Corrective Action