106 ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
N2 binary output objects – Drive
The following table lists the N2 Binary Output objects defined for the ACH580 drive.
N2 Binary Outputs:
Number Object Drive Parameter Range
BO1 STOP/START Command Word 0 = Stop, 1 = Start to Speed
BO2 FORWARD/REVERSE Command Word 0 = Forward, 1 = Reverse
BO3 PANEL LOCK Command Word 0 = Open, 1 = Locked
BO4 RUN PERMISSIVE Command Word 0 = Enable, 1 = Disable
BO5 REF1/REF2 SELECT Command Word 0 = Ref1, 1 = Ref2
BO6 FAULT RESET Command Word Change 0 -> 1 Resets
BO7 COMMAND RO 1 10.99, bit0 0 = Off, 1 = On
BO8 COMMAND RO 2 10.99, bit1 0 = Off, 1 = On
BO9 COMMAND RO 3 10.99, bit2 0 = Off, 1 = On
BO10 COMMAND RO 4 10.99, bit3 0 = Off, 1 = On
BO11 COMMAND RO 5 10.99, bit4 0 = Off, 1 = On
BO12 COMMAND RO 6 10.99, bit5 0 = Off, 1 = On
BO13 RESET RUN TIME Indirectly mapping 0 = N/A, 1 = On (Reset Run Time)
BO14 RESET KWH COUNT Indirectly mapping 0 = N/A, 1 = On (Reset kWh Count)
BO15 PRC PID SELECT 40.57 (indirectly) 0 = SET2, 1 = SET2
BO16 N2 LOCAL CTL (Note 1) DCU Control Word,
BIT16
0 = Auto, 1 = N2
BO17 N2 LOCAL REF (Note 1) DCU Control Word,
BIT17
0 = Auto, 1 = N2
BO18 SAVE PARAMETERS 96.07 (indirectly) 0 = N/A, 1 = On (Save Parameters)
BO19 READ MB N/A 0 = NO, 1 = READ
BO20 WRITE MB N/A 0 = NO, 1 = WRITE
1) N2 LOCAL CTL and N2 LOCAL REF have priority over drive input terminals. Use these binary
outputs for temporary N2 control of the drive when
COMM is not the selected control source.