ACH580 E-Clipse bypass and packaged drive user manual 111
Embedded fieldbus
N2 binary output objects – Bypass
The following table lists the N2 Binary Output objects defined for the ABB E-Clipse
bypass.
BI16 RELAY 1 STATUS 0104 (bit mask 1) 1 = On
BI17 RELAY 2 STATUS 0104 (bit mask 2) 1 = On
BI18 RELAY 3 STATUS 0104 (bit mask 4) 1 = On
BI19 RELAY 4 STATUS 0104 (bit mask 8) 1 = On
BI20 RELAY 5 STATUS 0104 (bit mask 10h) 1 = On
BI21 BYPASS MODE Status Word 0 = Drive mode, 1 = Bypass mode
BI22 SYS UNDERLOAD Status Word 1 = System Underload
BI23 SYS FAULT Status Word 1 = System Fault
BI24 BYPASS RUNNING Status Word 1 = Bypass Running
N2 Binary Outputs:
Number Object Drive Parameter Range
BO1 SYSTEM START Command Word 1 = Started
BO2 SYS RUN PERMISSIVE Command Word 1 = Enable
BO3 SYSTEM RESET Command Word Change 0 -> 1 Resets
BO4 OVERRIDE Command Word 1 = Override
BO5 COMMAND RO 1 107 (bit mask 1) 1 = On
BO6 COMMAND RO 2 107 (bit mask 2) 1 = On
BO7 COMMAND RO 3 107 (bit mask 4) 1 = On
BO8 COMMAND RO 4 107 (bit mask 8) 1 = On
BO9 COMMAND RO 5 107 (bit mask 10h) 1 = On
BO10 SYS INTERLOCK 1 Command Word 1 = Enable
BO11 SYS INTERLOCK 2 Command Word 1 = Enable
BO12 SYS INTERLOCK 3 Command Word 1 = Enable
BO13 SYS INTERLOCK 4 Command Word 1 = Enable
BO14 RESET KW HOURS 0106 Bypass-mode kilowatt hours - RESET
BO15 RESET RUN TIME 0108 0...65535 - RESET
BO16 PAR LOCK 1619 0 = LOCKED, 1 = OPEN
BO17 N2 LOCAL MODE Command Word 0 = AUTO, 1 = N2 LOCAL
BO18 READ MB N/A 0 = NO, 1 = READ
BO19 WRITE MB N/A 0 = NO, 1 = WRITE
N2 Binary Inputs:
Number Object Drive Parameter Range