ACH580 E-Clipse bypass and packaged drive user manual 117
Embedded fieldbus
Activate drive control functions
Controlling the drive
Fieldbus control of various drive functions requires configuration to:
• Tell the drive to accept fieldbus control of the function.
• Define as a fieldbus input, any system data required for control (drive only or
system)
• Define as a fieldbus output, any control data required by the drive.
The following sections describe the configuration required for each control function.
Note: The user should change only the parameters for the functions you wish to
control via BACnet. All other parameters should typically remain at factory default.
Start/stop direction control – Drive
Using the fieldbus for start/stop/direction control of the drive requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied command(s) in the appropriate location.
Input reference select
Using the fieldbus for start/stop/direction control of the drive requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied command(s) in the appropriate location.)
Bypass Parameter Value Description
BACnet
Access Point
1601 START/STOP 2 (COMM) Start/Stop by fieldbus with Ext1 or Ext2
1
selected
BV10
1625 COMM CTRL 0 (Drive
Only)
1 (System)
1625 = 0 for control signals (Start/Stop and
enables) to go to drive only
1625 = 1 for control signals to go to the
system (drive or bypass, depending on
keypad mode selection)
N/A
1) Ext1 = Ref 1
Ext 2 = Ref 2; Ref 2 normally used for PID setpoint commands.
Scalar Control
(Group 28)
Vector Control
(Group 22)
Value
Ext1/Ext2 Select 19.11 32, EFB MCW bit 11
Ext1
Ref1 28.11 22.11
Flexibility to write to 3.09
(EFBRef1) or 3.10
(EFBRef2)
Ref2 28.12 22.12
Ext2
Ref1 28.15 22.15
Ref2 28.16 22.16