ACH580 E-Clipse bypass and packaged drive user manual 143
Embedded fieldbus
attempt to read or write outside the parameter addresses, the Modbus interface
returns an exception code to the controller.
Register addressing is done as follows:
For drive parameters use: 400000 + 256 * parameter group + parameter index.
For example: parameter 22.80 would be mapped to register 400000 + 256 *
22 + 80 = 405712.
For bypass parameters use: 400000 + 256 * (parameter group + 128) +
parameter index.
For example: bypass parameter 01.11 would be mapped to register 400000 +
256 * (1 + 128) + 11 = 433035.
The following table summarizes the 4xxxxx drive control registers 400001…400099
(for 4xxxxx registers above 400099, see the drive parameter list, e.g. 400258 is
parameter 0102):
Modbus Register Access Remarks
400001 ABB DRIVES
PROFILE CONTROL
WORD
R/W Maps directly to the profile’s Control Word. Supported
only if bypass parameter 5825 = 0 or 2 (ABB drive
profile). Bypass parameter 5318 holds a copy in hex
format.
400002 Reference 1 R/W Range = 0...+20000 (scaled to +maximum reference),
or -20000...0 (scaled to -maximum reference). Where:
maximum reference is drive parameter 46.01, Speed
scaling if control mode is vector or parameter 46.02,
Frequency scaling if control mode is scalar.
400003 Reference 2 R/W Range = 0...+10000 (scaled to +maximum reference),
or -10000...0 (scaled to -maximum reference). Where:
maximum reference is drive parameter 46.01, Speed
scaling if control mode is vector or parameter 46.02,
Frequency scaling if control mode is scalar.
400004 ABB DRIVES
PROFILE STATUS
WORD
R Maps directly to the profile‘
S STATUS WORD.
Supported only if bypass parameter 5825 = 0 or 2 (ABB
bypass profile). Bypass parameter 5819 holds a copy in
hex format.
400005
1
Actual 1.
(select using drive
parameter 58.28,
EFB act1 type)
R By default, stores a copy of speed or frequency. Use
drive parameter 58.28 to select a different value.
400006
2
Actual 2.
(select using drive
parameter 58.29,
EFB act2 type)
R By default, stores nothing. Use drive parameter 58.29
to select a value.
400007 Actual 3.
(select using bypass
parameter 58107)
R By default, stores nothing. Use bypass parameter 5312
to select an actual value for this register.
400008 Actual 4.
(select using bypass
parameter 58108)
R By default, stores nothing. Use bypass parameter 5313
to select an actual value for this register.
400009 Actual 5.
(select using bypass
parameter 58109)
R By default, stores nothing. Use bypass parameter 5314
to select an actual value for this register.
400010 Actual 6.
(select using bypass
parameter 58110)
R By default, stores nothing. Use bypass parameter 5315
to select an actual value for this register.