60 ACH580 E-Clipse bypass and packaged drive user manual
Parameters
Group 03: Status
Group 03: Status
Code Name Resolution Range Default Description
0301 FBUS CW 1 b0: 1 = Start
b1: 1 = Fault reset
b2: 1 = Run disable
b3: 1 = Field bus local
b4: 1 = Start disable 1
b5: 1 = Start disable 2
b6: 1 = Start disable 3
b7: 1 = Start disable 4
b8: 1 = Override 2
b9: 1 = Link On
b10 - b15: not used
0 Control word 1 from field
bus
0303 FBUS SW 1 b0: 1 = Ready
b1: 1 = Enabled
b2: 1 = Started
b3: 1 = Running
b4: 1 = Field bus local
b5: 1 = Fault
b6: 1 = Warning
b7: 1 = Notice
b8: 1 = Request control
b9: 1 = Override
b10: 1 = Powered up
b11: 1 = Bypass mode
b12: 1 = Panel local mode
b13 - 15: not used
0 Status word 1 to field
bus
0305 FLT WORD 1 b0: 1 = Coil current measurement
b1: 1 = Bypass contact stuck
b2: 1 = Drive contact stuck
b3: 1 = Bypass coil open
b4: 1 = Drive coil open
b5: 1 = Undervoltage
b6: not used
b7: 1 = Drive AI2 fault
b8: 1 = Motor overload
b9: 1 = Input phase A loss
b10: 1 = Input phase B loss
b11:1 = Input phase C loss
12: 1 = Drive 1st start fault
b13: 1 = coil power supply fault
b14: not used
b15: 1 = Earth fault
0 Bypass fault status,
word 1
0306 FLT WORD 2 b0: 1 = Motor Underload
b1: 1 = Max cycling fault
b2: 1 = Drive link fault
b3: 1 = Reverse rotation
b4: 1 = Phase A current
measurement
b5: 1 = Phase C current
measurement
b6: 1 = Bypass coil shorted
b7: 1 = Drive coil shorted
b8: not used
b9: not used
b10: 1 = Invalid sub-assembly
b11: 1 = Serial 1 Err
b12: 1 = EFB Config File
b13: 1 = Force Trip
b14: 1 = EFB 1
b15: 1 = EFB 2
0 Bypass fault status,
word 2