ACH580 E-Clipse bypass and packaged drive user manual 61
Parameters
Group 04: Fault Log
0307 FLT WORD 3 — b0: 1 = EFB 3
b1: 1 = Open motor phase
b2: not used
b3: not used
b4: 1 = Control board
temperature
b5: not used
b6: not used
b7: not used
b8: 1 = RBIO ID error
b9: 1 = Stack overflow
b10: 1 = Timed scan
overflow
b11: 1 = Serial flash corrupt
b12: 1 = Unknown drive
b13: 1 = Unknown bypass
b14 - b15: not used
0 Bypass fault status,
word 3
0308 WRN WORD 1 — b0: 1 = Input phase A loss
b1: 1 = Input phase B loss
b2: 1 = Input phase C loss
b3: 1 = Auto transfer active
b4: 1 = External Comm
Error
b5: 1 = Permissive
b6: 1 = PCB Temp
b7: 1 = Drive Setup
b8: 1 = Bypass run delay
b9: 1 = Motor Temp
b10: 1 = Underload
b11: 1 = Bypass disabled
b12: 1 = Drive link error
b13: 1 = Drive test
b14: 1 = Drive 1st start
needed
b15: 1 = Low input voltage
0 Bypass warning status,
word 1
0309 WRN WORD 2 — b0: not used
b1: not used
b2: Override 1
b3: Override 2
b4: 1 = Interlock 1
b5: 1 = Interlock 2
b6: 1 = Interlock 3
b7: 1 = Interlock 4
b8: 1 = Mode auto lock
b9: 1 = Mode local lock
b10: 1 = Comm config error
b11: 1 = FIG parameter
configuration
b12: 1 = Drive faulted
b13 - b15: not used
0 Bypass warning status,
word 2
Group 04: Fault Log
Code Name Resolution Range Default Description
0401 LAST FAULT 1 3001 - 3999
See 'Faults' page
0 Last fault declared
0402 F1 TIME 1 1, days ago 0 - 65535 0 Time since last fault, days
0403 F1 TIME 2 2, ago 00:00:00 - 23:59:58 0 Time since last fault,
hr:min:sec
0404 F1 VOLTAGE 1V 0 - 1200V 0 Input voltage at last fault
0405 F1 CURRENT 0.1A 0.0 - 6553.5A 0 Motor current at last fault
0406 F1 EVENT 1 — See parameter 501 0 Last event status before last
fault
0407 F1 E1 TIME 2, before 00:00:00 - 23:59:58 0 Time before last fault of last
event: hr:min:sec if time < 1
day
1, days before 0 - 9999 days if time >= 1 day
0408 F1 EVENT 2 — See parameter 501 0 2nd to last event status before
last fault
Group 03: Status
Code Name Resolution Range Default Description