ACH580 E-Clipse bypass and packaged drive user manual 63
Parameters
Group 14: Relay Outputs
0508 E3 TIME 1 1, days ago 0 - 65535 0 Time since 3rd last event,
days
0509 E3 TIME 2 2, ago 00:00:00 - 23:59:58 0 Time since 3rd last event,
hr:min:sec
0510 EVENT 4 — See parameter 501 0 Status of 4th to last event
0511 E4 TIME 1 1, days ago 0 - 65535 0 Time since 4th last event,
days
0512 E4 TIME 2 2, ago 00:00:00 - 23:59:58 0 Time since 4th last event,
hr:min:sec
Group 14: Relay Outputs
Code Name Resolution Range Default Description
1401 RO1 SELECT 1 0 = NOT SEL
1 = SYS READY
2 = SYS RUNNING
3 = SYS STARTED
4 = BYPASS SEL
5 = BYPASS RUN
6 = BYPASS FLT
7 = BYP NOT FLT
8 = BYPASS WRNG
9 = DRIVE FAULT
10 = DRV NOT FLT
11 = DRIVE WARNING
12 = OVERRIDE
13 = BYPASS HAND
14 = BYPASS OFF
15 = BYPASS AUTO
16 = COMM CTRL
17 = SYS WARNING
18 = BYP FLT/WRN
19 = BYP OVERLD
20 = BYP UNDERLD
21 = PCB OVERTMP
22 = SYS UNDERLD
23 = SYSTEM FLT
24 = SYS FLT/WRN
25 = SYS EXT CTL
26 = SYS OVERLD
27 = CONTACT FLT
28 = SYS NOT FLT
29 = DRV LNK ERR
30 = EXT COMM LS
31 = OVRD2 STOP
32 = OVRD2 ENAB
BYP NOT
FLT
(7)
Selects function for digital
output. Define the event or
condition that activates
relay 1.
1402 R1 ON DLY 0.1 sec 0-3600.0s 0s Delay from active state to
active output.
1403 R1 OFF DLY 0.1 sec 0-3600.0s 0s Delay from inactive state
to inactive output.
1404 RO2 SELECT 1 See RO 1 Select. SYS
RUNNING
(2)
1405 R2 ON DLY 0.1 sec 0-3600.0s 0s Delay from active state to
active output.
1406 R2 OFF DLY 0.1 sec 0-3600.0s 0s Delay from inactive state
to inactive output.
1407 RO3 SELECT 1 See RO 1 Select. SYS
STARTED
(3)
1408 R3 ON DLY 0.1 sec 0-3600.0s 0s Delay from active state to
active output.
1409 R3 OFF DLY 0.1 sec 0-3600.0s 0s Delay from inactive state
to inactive output.
1410 RO4 SELECT 1 See RO 1 Select. BYPASS
SEL
(4)
Group 05: Event Log
Code Name Resolution Range Default Description