ACH580 E-Clipse bypass and packaged drive user manual 65
Parameters
1616 DISP WRNGS 1 0 = DISABLE
1 = ENABLE
ENABLE
(1)
Enables warnings to be
displayed:
INP PHASE A LOSS,
INP PHASE B LOSS,
INP PHASE C LOSS,
MTR OVERLOAD,
BYPASS DISABLED,
DRIVE SETUP,
PCB TEMP
DRIVE LINK ERROR
DRIVE FAULTED
1617 DRIVE TEST 1 0 = DISABLE
1 = ENABLE
DISABLE
(0)
Enables drive test mode. Drive
contactor is opened.
1618 PASS CODE 1 0 - 65535 123 Pass code entry to edit panel
lock parameter and view/edit
security lock parameters. The
security parameters are
1640 – 1644. Default: 123
1619 PAR LOCK 1 0 = LOCKED
1 = OPEN
OPEN
(1)
When switched to "LOCKED"
prevents parameter changes
from panel. Does not affect to
Field Bus writes, expect
changing the lock value itself:
correct password must always
be set first, even in case of Field
Bus.
1620 PERMSV TXT 1 0 = PERMISSIVE
1 = DAMPER
END SWTCH
2 = VALVE
OPENING
3 = PRE-LUBE
CYCLE
PERMISSIVE
(0)
Alternative text choices for
warning 4006.
1621 INTLK1 TXT 1 0 = INTERLOCK 1
1 = VIBRATION
SWITCH
2 = FIRESTAT
3 = FREEZESTAT
4 =
OVERPRESSUR
E
5 = VIBRATION
TRIP
6 = SMOKE
WARNING
7 = SAFETY
OPEN
8 = LOW
SUCTION
INTERLOCK 1
(0)
Alternative text choices for
warning 4021.
1622 INTLK2 TXT 1 0 = INTERLOCK 2
...
INTERLOCK 2
(0)
Alternative text choices for
warning 4022.
See parameter 1621 for range.
1623 INTLK3 TXT 1 0 = INTERLOCK 3
...
INTERLOCK 3
(0)
Alternative text choices for
warning 4023.
See parameter 1621 for range.
1624 INTLK4 TXT 1 0 = INTERLOCK 4
...
INTERLOCK 4
(0)
Alternative text choices for
warning 4024.
See parameter 1621 for range.
1625 COMM CTRL 1 0 = DRIVE ONLY
1 = SYSTEM
DRIVE ONLY
(0)
Selects comm control mode. In
drive only mode, control of drive
is made through drive points,
and control of bypass over
comms is not possible. In
system mode, control of system
(bypass or drive) is made
through bypass points.
Group 16: System Control
Code Name Resolution Range Default Description