86 ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
Input reference select
Using the fieldbus to provide input references to the drive requires:
Drive parameter values set with the drive keypad as defined below.
Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
EFB Ref1/Ref2
Reference
As described earlier in Control interface, the REFERENCE word is a speed or
frequency reference.
Reference scaling
Where required, REFERENCES can be scaled. See the following, as appropriate:
Modbus Register 40002 in the Modbus protocol technical data – Drive only
section.
N2 analog output objects – Drive in the N2 protocol technical data – system
section.
The slope of points 60 and 61 in the BACnet protocol technical data – system
section.
The following table describes REFERENCE scaling for the ABB Drives profile.
Scalar Control
(Group 28)
Vector Control
(Group 22)
Value
Ext1/Ext2 Select 19.11 32, EFB MCW bit 11
Ext1
Ref1 28.11 22.11
Flexibility to write to 3.09
(EFBRef1) or 3.10
(EFBRef2)
Ref2 28.12 22.12
Ext2
Ref1 28.15 22.15
Ref2 28.16 22.16
Drive Parameter
Modbus
N2 BACnet
ABB DRV DCU Profile
19.11 Ext1/Ext2 Selection
40001 40031
BO5 BV13
bit11 bit5
3.09 EFB Ref1 40002 AO1 AV16
3.10 EFB Ref2 40003 AO2 AV17
ABB Drives Profile (EFB)
Reference Range
Reference
Type
Scalar Remarks
REF1
-32767…
+32767
Frequency -20000 = -(par 46.02)
+20000 = (par 46.02)
Final reference limited
by 30.13/30.14
Speed -20000 = -(par 46.01)
+20000 = (par 46.01)
Final reference limited
by 30.11/30.12
REF2
-32767…
+32767
Frequency -20000 = -(par 46.02)
+20000 = (par 46.02)
Final reference limited
by 30.13/30.14
Speed -20000 = -(par 46.01)
+20000 = (par 46.01)
Final reference limited
by 30.11/30.12